HowMuchDoINeed.co logo

Cable Size Calculator (UK)

What it does: Suggests a cable size from load, length and installation method using BS 7671 tables. Who it’s for: Electricians and informed DIYers in the UK (always have work checked by a qualified electrician).

This cable size calculator UK tool works out the minimum cable size you need from the voltage drop, current load, cable run length and installation method, following BS 7671 (IET Wiring Regulations 18th Edition). Supports Twin & Earth and SWA cables.

Part of:Electrical hub
kW
V
metres

How to Use This Calculator

What This Cable Size Calculator UK Tool Does

This cable size calculator UK tool takes the electrical load, cable run length and how the cable is installed, then works out the smallest cable that safely carries the current and keeps the voltage drop within the limits set by BS 7671 (the IET Wiring Regulations 18th Edition). It is the same two-part check a qualified electrician makes: current-carrying capacity first, then voltage drop.

How to Use This Calculator

  1. Cable Type – Twin & Earth is standard domestic wiring; SWA (Steel Wire Armoured) is used for outdoor runs, outbuildings and higher-current circuits.
  2. Installation Method – How the cable is routed. Clipped direct gives the best current rating; enclosed in insulated walls needs derating.
  3. Circuit Type – Non-lighting circuits allow up to 5% voltage drop; lighting circuits are limited to 3% (BS 7671 regulation 525.1).
  4. Ambient Temperature – The expected maximum surrounding air temperature. Hotter surroundings reduce the current a cable can carry.
  5. Number of Circuits & Layout – How many cables share the route and whether they are bunched or laid side by side. More cables grouped together means more derating.
  6. Power – The load in kilowatts (kW) the circuit will carry.
  7. Voltage – Supply voltage, normally 230 V in the UK (single phase).
  8. Cable Length – The one-way distance from the consumer unit to the final point of the circuit, in metres.

Common UK Cable Sizes and Typical Uses

Cable sizeTypical current rating*Common use
1.0 mm²~11–16 ALighting circuits
1.5 mm²~14–20 ALighting, immersion heater
2.5 mm²~18–27 ARing final (socket) circuits
4.0 mm²~25–37 ACooker (small), radial sockets
6.0 mm²~32–47 AShowers, small cookers
10 mm²~43–64 ALarge cookers, 9–10 kW showers
16 mm²~57–85 ASub-mains, EV chargers

*Current rating varies with installation method, grouping and ambient temperature – always use the calculator with your own figures rather than relying on the range above.

Worked Example

A 9.5 kW electric shower on a 230 V supply draws about 41 A (9500 ÷ 230). The cable is Twin & Earth clipped direct, run 18 m from the consumer unit, ambient 30 °C, on its own. A 6 mm² cable is rated around 47 A so it passes the current check, but over 18 m its voltage drop (7.3 mV/A/m × 41 A × 18 m ≈ 5.4 V, about 2.3%) is within the 5% limit – so 6 mm² is suitable. Increase the length to 30 m and voltage drop climbs to about 9 V (3.9%), still under 5%, but a longer run or a bigger shower can push you up to 10 mm². This is exactly the trade-off the calculator resolves for you.

Related Calculators

Wiring a bigger project? Try our pipe sizing calculator for plumbing runs, or plan the structure with the stud spacing calculator and timber fastener spacing calculator.

Common Questions

Is this a UK cable size calculator?

Yes. This cable size calculator UK tool is based on BS 7671 (IET Wiring Regulations 18th Edition) and UK cable data for Twin & Earth and SWA cables, using a 230 V single-phase supply and the 3% / 5% voltage drop limits used in UK domestic and light commercial work.

What is voltage drop and why does it matter?

Voltage drop is the reduction in voltage as electricity travels along a cable. Excessive voltage drop means appliances receive less than their rated voltage, which can cause poor performance, dimming lights, or overheating. BS 7671 limits it to 3% for lighting and 5% for other circuits.

What cable do I need for a cooker or shower?

A typical 9–10 kW electric shower or cooker on a 230 V supply draws around 40–45 A, usually requiring 10 mm² Twin & Earth cable clipped direct, though the actual size depends on cable run length, installation method, and grouping.

Do I need to apply correction factors?

Yes – BS 7671 requires correction for ambient temperature above 30 °C and for cables grouped together. This calculator applies both automatically based on your inputs.

Should I use this instead of a qualified electrician?

This tool gives a useful starting estimate but electrical work in the UK must comply with Part P of the Building Regulations. Always have cable sizing verified by a qualified electrician before installation.

Related calculators

Cable size chart & sizing guide

The calculator does the sums. These charts let you sanity-check the answer, see why a cable size was chosen and spot when an installation method changes everything.

Twin & earth cable size chart (BS 7671, 70 °C PVC)

Current-carrying capacity in amps (A) for flat twin & earth (6242Y) on a single-phase circuit, from BS 7671 Table 4D5. The installation method matters as much as the cable size. The same cable buried in insulation carries about half the current.

SizeClipped direct (Method C)In insulated stud wall, touching inner face (Method 102)Fully surrounded by insulation (Method 103)Voltage drop (mV/A/m)
1.0 mm²16 A13 A8 A44
1.5 mm²20 A16 A10 A29
2.5 mm²27 A21 A13.5 A18
4.0 mm²37 A27 A17.5 A11
6.0 mm²47 A35 A23.5 A7.3
10 mm²64 A47 A32 A4.4
16 mm²85 A63 A42.5 A2.8

Ratings are before correction factors for grouping, ambient temperature above 30 °C or partial burial in insulation. Apply those and the usable current falls further.

Typical cable sizes for common UK circuits

CircuitTypical breaker (MCB/RCBO)Typical cable
Lighting6 A1.0 or 1.5 mm² T&E
Ring final (sockets)32 A2.5 mm² T&E
Radial sockets (up to 50 m² floor area)20 A2.5 mm² T&E
Radial sockets (up to 75 m²)32 A4.0 mm² T&E
Immersion heater (3 kW)16 A2.5 mm² T&E + heat-resistant flex
Cooker (up to ~10 kW after diversity)32 A6.0 mm² T&E
Electric shower 8.5–9.5 kW40–45 A10 mm² T&E
EV charger 7 kW32 A6 mm² T&E, or 6–10 mm² SWA on longer runs
Garden office / outbuilding feed32–40 A6–10 mm² 3-core SWA, sized for length

These are starting points only. Long runs, insulation and grouping often push the size up a step. That's exactly what the voltage-drop check in the calculator catches. Most new circuits in England and Wales are notifiable under Part P, so have them installed or certified by a registered electrician.

Worked example: voltage drop on a garden office feed

A 32 A supply to a garden office 35 m (115 ft) from the consumer unit, run in 6 mm² SWA (voltage drop about 7.3 mV/A/m):

Voltage drop = 7.3 × 32 × 35 ÷ 1000 = 8.2 V, which is 3.6% of 230 V.

The limit for a final circuit other than lighting is 5% (11.5 V), so 6 mm² passes. Stretch the run to 50 m and the drop becomes 11.7 V (5.1%), which fails. You'd then step up to 10 mm² (4.4 mV/A/m), giving 7.0 V (3.1%). Lighting circuits have a tighter limit of 3% (6.9 V).

DC cable sizing for solar, leisure batteries and 12 V / 24 V systems

Low-voltage DC is where people most often undersize cable. Lose a single volt and that's over 8% of a 12 V system. For DC, size by voltage drop using:

Cable size (mm²) = (2 × length (m) × current (A) × 0.0175) ÷ allowed voltage drop (V)

The 2 accounts for the out-and-back run, and 0.0175 is the resistivity of copper (Ω·mm²/m). Aim for 3% or less, or 1% on battery-to-inverter runs.

Example: a 12 V, 20 A load 5 m (16 ft) from the battery with a 3% (0.36 V) allowance: 2 × 5 × 20 × 0.0175 ÷ 0.36 = 9.7 mm², so use 10 mm² (the nearest AWG is 7 AWG; in practice choose 6 AWG).

Metric sizeNearest AWG (North America)
1.5 mm²16 AWG
2.5 mm²14 AWG
4 mm²12 AWG
6 mm²10 AWG
10 mm²8 AWG (next size up: 6 AWG)
16 mm²6 AWG
25 mm²4 AWG

Solar PV strings normally use 4 mm² or 6 mm² double-insulated PV1-F / H1Z2Z2-K cable. Strings run at high voltage and low current, so voltage drop is rarely the limit there.

US wire sizes (NEC) for comparison

Copper wire (NM-B)Max breakerTypical use
14 AWG15 ALighting, general outlets
12 AWG20 AKitchen, bathroom and garage outlets
10 AWG30 AWater heater, dryer
8 AWG40 ARange / cooktop
6 AWG55 ASub-panel, large range, EV charger

NM-B ampacity is limited to the 60 °C column of NEC Table 310.16. Always follow local code and your inspector.

Common mistakes

  • Ignoring insulation. A 2.5 mm² cable fully buried in loft insulation is only good for about 13.5 A.
  • Forgetting the run length. Current rating can pass while voltage drop fails on runs over about 30 m (100 ft).
  • Sizing the cable to the load, not the breaker. The cable must be protected by the device, so the cable rating has to be at least the breaker rating.
  • Using AC tables for DC. Low-voltage DC needs the voltage-drop formula above.

Related: voltage drop calculator, cable length calculator, breaker size calculator.

Further Reading