What it does: Suggests a cable size from load, length and installation method using BS 7671 tables. Who it’s for: Electricians and informed DIYers in the UK (always have work checked by a qualified electrician).
This cable size calculator UK tool works out the minimum cable size you need from the voltage drop, current load, cable run length and installation method, following BS 7671 (IET Wiring Regulations 18th Edition). Supports Twin & Earth and SWA cables.
This cable size calculator UK tool takes the electrical load, cable run length and how the cable is installed, then works out the smallest cable that safely carries the current and keeps the voltage drop within the limits set by BS 7671 (the IET Wiring Regulations 18th Edition). It is the same two-part check a qualified electrician makes: current-carrying capacity first, then voltage drop.
| Cable size | Typical current rating* | Common use |
|---|---|---|
| 1.0 mm² | ~11–16 A | Lighting circuits |
| 1.5 mm² | ~14–20 A | Lighting, immersion heater |
| 2.5 mm² | ~18–27 A | Ring final (socket) circuits |
| 4.0 mm² | ~25–37 A | Cooker (small), radial sockets |
| 6.0 mm² | ~32–47 A | Showers, small cookers |
| 10 mm² | ~43–64 A | Large cookers, 9–10 kW showers |
| 16 mm² | ~57–85 A | Sub-mains, EV chargers |
*Current rating varies with installation method, grouping and ambient temperature – always use the calculator with your own figures rather than relying on the range above.
A 9.5 kW electric shower on a 230 V supply draws about 41 A (9500 ÷ 230). The cable is Twin & Earth clipped direct, run 18 m from the consumer unit, ambient 30 °C, on its own. A 6 mm² cable is rated around 47 A so it passes the current check, but over 18 m its voltage drop (7.3 mV/A/m × 41 A × 18 m ≈ 5.4 V, about 2.3%) is within the 5% limit – so 6 mm² is suitable. Increase the length to 30 m and voltage drop climbs to about 9 V (3.9%), still under 5%, but a longer run or a bigger shower can push you up to 10 mm². This is exactly the trade-off the calculator resolves for you.
Wiring a bigger project? Try our pipe sizing calculator for plumbing runs, or plan the structure with the stud spacing calculator and timber fastener spacing calculator.
Yes. This cable size calculator UK tool is based on BS 7671 (IET Wiring Regulations 18th Edition) and UK cable data for Twin & Earth and SWA cables, using a 230 V single-phase supply and the 3% / 5% voltage drop limits used in UK domestic and light commercial work.
Voltage drop is the reduction in voltage as electricity travels along a cable. Excessive voltage drop means appliances receive less than their rated voltage, which can cause poor performance, dimming lights, or overheating. BS 7671 limits it to 3% for lighting and 5% for other circuits.
A typical 9–10 kW electric shower or cooker on a 230 V supply draws around 40–45 A, usually requiring 10 mm² Twin & Earth cable clipped direct, though the actual size depends on cable run length, installation method, and grouping.
Yes – BS 7671 requires correction for ambient temperature above 30 °C and for cables grouped together. This calculator applies both automatically based on your inputs.
This tool gives a useful starting estimate but electrical work in the UK must comply with Part P of the Building Regulations. Always have cable sizing verified by a qualified electrician before installation.
The calculator does the sums. These charts let you sanity-check the answer, see why a cable size was chosen and spot when an installation method changes everything.
Current-carrying capacity in amps (A) for flat twin & earth (6242Y) on a single-phase circuit, from BS 7671 Table 4D5. The installation method matters as much as the cable size. The same cable buried in insulation carries about half the current.
| Size | Clipped direct (Method C) | In insulated stud wall, touching inner face (Method 102) | Fully surrounded by insulation (Method 103) | Voltage drop (mV/A/m) |
|---|---|---|---|---|
| 1.0 mm² | 16 A | 13 A | 8 A | 44 |
| 1.5 mm² | 20 A | 16 A | 10 A | 29 |
| 2.5 mm² | 27 A | 21 A | 13.5 A | 18 |
| 4.0 mm² | 37 A | 27 A | 17.5 A | 11 |
| 6.0 mm² | 47 A | 35 A | 23.5 A | 7.3 |
| 10 mm² | 64 A | 47 A | 32 A | 4.4 |
| 16 mm² | 85 A | 63 A | 42.5 A | 2.8 |
Ratings are before correction factors for grouping, ambient temperature above 30 °C or partial burial in insulation. Apply those and the usable current falls further.
| Circuit | Typical breaker (MCB/RCBO) | Typical cable |
|---|---|---|
| Lighting | 6 A | 1.0 or 1.5 mm² T&E |
| Ring final (sockets) | 32 A | 2.5 mm² T&E |
| Radial sockets (up to 50 m² floor area) | 20 A | 2.5 mm² T&E |
| Radial sockets (up to 75 m²) | 32 A | 4.0 mm² T&E |
| Immersion heater (3 kW) | 16 A | 2.5 mm² T&E + heat-resistant flex |
| Cooker (up to ~10 kW after diversity) | 32 A | 6.0 mm² T&E |
| Electric shower 8.5–9.5 kW | 40–45 A | 10 mm² T&E |
| EV charger 7 kW | 32 A | 6 mm² T&E, or 6–10 mm² SWA on longer runs |
| Garden office / outbuilding feed | 32–40 A | 6–10 mm² 3-core SWA, sized for length |
These are starting points only. Long runs, insulation and grouping often push the size up a step. That's exactly what the voltage-drop check in the calculator catches. Most new circuits in England and Wales are notifiable under Part P, so have them installed or certified by a registered electrician.
A 32 A supply to a garden office 35 m (115 ft) from the consumer unit, run in 6 mm² SWA (voltage drop about 7.3 mV/A/m):
Voltage drop = 7.3 × 32 × 35 ÷ 1000 = 8.2 V, which is 3.6% of 230 V.
The limit for a final circuit other than lighting is 5% (11.5 V), so 6 mm² passes. Stretch the run to 50 m and the drop becomes 11.7 V (5.1%), which fails. You'd then step up to 10 mm² (4.4 mV/A/m), giving 7.0 V (3.1%). Lighting circuits have a tighter limit of 3% (6.9 V).
Low-voltage DC is where people most often undersize cable. Lose a single volt and that's over 8% of a 12 V system. For DC, size by voltage drop using:
Cable size (mm²) = (2 × length (m) × current (A) × 0.0175) ÷ allowed voltage drop (V)
The 2 accounts for the out-and-back run, and 0.0175 is the resistivity of copper (Ω·mm²/m). Aim for 3% or less, or 1% on battery-to-inverter runs.
Example: a 12 V, 20 A load 5 m (16 ft) from the battery with a 3% (0.36 V) allowance: 2 × 5 × 20 × 0.0175 ÷ 0.36 = 9.7 mm², so use 10 mm² (the nearest AWG is 7 AWG; in practice choose 6 AWG).
| Metric size | Nearest AWG (North America) |
|---|---|
| 1.5 mm² | 16 AWG |
| 2.5 mm² | 14 AWG |
| 4 mm² | 12 AWG |
| 6 mm² | 10 AWG |
| 10 mm² | 8 AWG (next size up: 6 AWG) |
| 16 mm² | 6 AWG |
| 25 mm² | 4 AWG |
Solar PV strings normally use 4 mm² or 6 mm² double-insulated PV1-F / H1Z2Z2-K cable. Strings run at high voltage and low current, so voltage drop is rarely the limit there.
| Copper wire (NM-B) | Max breaker | Typical use |
|---|---|---|
| 14 AWG | 15 A | Lighting, general outlets |
| 12 AWG | 20 A | Kitchen, bathroom and garage outlets |
| 10 AWG | 30 A | Water heater, dryer |
| 8 AWG | 40 A | Range / cooktop |
| 6 AWG | 55 A | Sub-panel, large range, EV charger |
NM-B ampacity is limited to the 60 °C column of NEC Table 310.16. Always follow local code and your inspector.
Related: voltage drop calculator, cable length calculator, breaker size calculator.