Calculate the voltage drop and percentage loss along a cable run from the conductor size, current and length, for both UK and US wiring.
The calculator works out the conductor resistance, the voltage lost along the run, the percentage drop and the voltage left at the load. UK guidance (BS 7671) limits voltage drop to 3% for lighting and 5% for other circuits; the US NEC recommends a maximum of 3% on a branch circuit.
UK wiring regulations (BS 7671) recommend no more than 3% for lighting and 5% for other circuits. The US NEC recommends a maximum of 3% on a branch circuit and 5% overall including the feeder.
Excess voltage drop means appliances get less than their rated voltage, causing dim lights, slow motor starts, overheating and wasted energy. Long cable runs are the most common cause.
Use a larger conductor, shorten the cable run, switch from aluminium to copper, or raise the supply voltage (for example wiring a load at 240 V instead of 120 V in the US).
Yes. Switch the wiring standard to enter conductor size in mm² with the run in metres (UK) or in AWG/kcmil with the run in feet (US). The result is shown in volts and as a percentage either way.
This tool tells you the voltage drop for a cable you have already chosen. The Cable Size calculator works in reverse – it finds the smallest conductor that keeps the drop within limits for your load.
Calculate the minimum cable size based on voltage drop, current load, cable run length and installation method per BS 7671 / IET Wiring Regulations.
OpenWork out the correct circuit breaker or fuse rating (MCB / breaker) for a load from its power, voltage and continuous-load factor.
OpenCheck how many cables or conductors fit in a conduit and the percentage fill against the 40% maximum, for UK and US conduit sizes.
Open