HowMuchDoINeed.co logo

Insulation Calculator

What it does: Calculate the amount of insulation rolls, batts, or boards needed for walls, floors and lofts. Who it’s for: Decorators, plasterers and DIYers finishing rooms.

Part of:Interior hub
sq ft
in

How to Use This Calculator

What this insulation calculator does

This insulation calculator works out how much insulation you need by area, and helps you choose a thickness for lofts (attics), walls and floors. It works with rolls, batts (slabs) and boards, in metric or imperial, using both UK depths (mm) and US R-values.

How to use it

  1. Enter the total area to insulate.
  2. Select the insulation type and thickness.
  3. Read the number of rolls/packs to buy.

Recommended insulation levels

LocationUK depthUS R-value
Loft / attic270 mmR-38 to R-49
Cavity wall50–100 mmR-13 to R-21
Suspended floor100 mmR-19 to R-25

Worked example

A loft of 50 m² needing 270 mm often uses a first layer between the joists and a second layer laid across them. Rolls state their coverage per pack, so divide the area by the pack coverage and round up.

Tips

  • Higher R-value (or lower U-value) means better insulation.
  • Don't squash insulation – compressing it reduces its performance.
  • Leave ventilation gaps at the eaves so the roof space can breathe.

Common Questions

How much insulation do I need for a loft?

Measure the loft floor area and divide by the roll coverage area. Standard UK loft insulation is 270 mm thick.

What R-value do I need?

R-38 to R-60 for attics, R-13 to R-23 for walls, R-25 to R-30 for floors in most US climate zones.

Can I lay new insulation over old?

Yes, as long as the existing insulation is dry and in good condition. Lay the new rolls perpendicular to the old.

Which way should loft insulation be laid?

Lay the first layer between the joists, then a second layer at right angles across the joists to cover the cold bridges. Keep insulation clear of eaves vents and recessed lights.

What thickness of loft insulation is recommended?

Current UK guidance is around 270 mm of mineral wool for a loft; walls and floors use thinner boards or batts to suit the cavity.

Related calculators

Insulation reference: thickness, R-values & U-values

Insulation is specified as a thermal performance target. In the UK and Europe that is a U-value (lower is better); in North America it is an R-value (higher is better). These tables connect thickness, material and target.

Thermal conductivity and thickness by material

MaterialTypical λ (W/m·K)R per 100 mm (m²K/W)US R per inch
Glass mineral wool loft roll0.040–0.0442.3–2.5R-3.1 to 3.4
Stone wool (rock wool) slab0.035–0.0382.6–2.9R-3.8 to 4.2
EPS polystyrene0.032–0.0382.6–3.1R-3.8 to 4.4
XPS polystyrene0.029–0.0342.9–3.4R-5
PIR / polyiso board (foil faced)0.0224.5R-6 to 6.5
Closed-cell spray foam0.022–0.0283.6–4.5R-6 to 7
Sheep's wool / wood fibre0.038–0.0422.4–2.6R-3.5

To convert: US R-value ≈ metric RSI × 5.678. R-38 is about RSI 6.7.

Typical targets by element

ElementUK (England) new work / upgradesUS (IECC, mid climate zones 4–5)
Loft / attic at ceilingU 0.16 W/m²K, ≈ 270–300 mm mineral woolR-49 to R-60 (≈ 13–16 in loose fill)
Pitched roof at raftersU 0.15–0.18, ≈ 120–150 mm PIR between + underR-38 to R-49
External wallsU 0.18–0.30, 100 mm PIR or full-fill 100–150 mm cavity battsR-20 cavity or R-13 + R-5 continuous
Ground floorU 0.13–0.25, 75–150 mm PIR under screedR-10 to R-19
Garden room / log cabinAim for roughly the same as an extension if used year roundSame as a heated room in your zone

Targets change with each edition of Building Regulations (Part L) and the IECC, and differ in Scotland, Wales and each US state or Canadian province. Check the current figures for your area.

Worked example: topping up a loft

A loft 8 × 5 m (26 ft × 16 ft 5 in) with 100 mm of old wool between the joists. Target ≈ 270 mm.

  1. Area: 40 m² (430 ft²).
  2. Top-up needed: 170 mm. Lay 170–200 mm rolls across the joists (cross-laying stops cold bridging through the timber).
  3. A typical 200 mm roll covers about 5.5–6 m², so 40 ÷ 5.8 = 6.9, which means 7 rolls (plus one spare for eaves cuts).
  4. Keep a 50 mm (2 in) air gap at the eaves with eaves vents so the roof stays ventilated.

Common mistakes

  • Compressing loft roll under boards. Squashed insulation loses much of its value; use loft legs to raise storage decking.
  • Blocking ventilation at the eaves, which causes condensation in the roof.
  • No vapour control layer on the warm side of PIR in walls and rafters.
  • Covering downlights and cables. Use fire-rated downlight hoods, and don't bury cables that the cable size was not de-rated for.

Related: roof pitch calculator, drywall / plasterboard calculator, cable size calculator.

Further Reading